Daikin FXSQ100A concealed ceiling VRV indoor unit
The FXSQ100A provides ducted air distribution while keeping the indoor unit concealed above the ceiling. Its 11.2 kW cooling and 12.5 kW heating ratings support selection for the room load, while adjustable external static pressure allows the duct design to be considered alongside airflow and sound. The specifications below follow the FXSQ100A2VEB model in the supplied 2021 technical databook.
Cooling, heating and indoor power input
| Listed product / databook model | FXSQ100A / FXSQ100A2VEB |
|---|---|
| Total cooling capacity, high fan speed | 11.2 kW (approximately 38,200 Btu/h) |
| Total heating capacity, high fan speed | 12.5 kW |
| Indoor power input, cooling / heating at 50 Hz | 0.290 / 0.285 kW |
Btu/h is converted from the published kW figure and rounded to the nearest 100 Btu/h. Indoor power input is not the consumption of the complete VRV system. Use the manufacturer capacity tables and the selected outdoor-unit combination for project design conditions.
Airflow and medium static pressure
| Airflow, cooling H / M / L at 50 Hz | 32 / 27 / 23 m³/min |
|---|---|
| Factory external static pressure | 40 Pa |
| Maximum external static pressure | 150 Pa |
| Cooling sound pressure H / M / L | 36 / 34 / 31 dB(A) |
| Fan motor | Brushless DC, three speed steps |
External static pressure can be adjusted through a wired remote controller to suit the required supply airflow. The catalogue also describes automatic airflow adjustment. Check the fan curves against the proposed ducts and grilles; the maximum pressure figure alone does not establish the available airflow for every installation. Sound figures are manufacturer test values, and installed room acoustics will affect perceived noise.
Dimensions, supply and drainage
| Indoor body H × W × D | 245 × 1,400 × 800 mm |
|---|---|
| Built-in height | 300 mm, as stated in the databook feature section |
| Unit weight | 46 kg |
| Electrical supply | 1 phase; 220–240 V at 50 Hz / 220 V at 60 Hz |
| Refrigerant | R-410A |
| Liquid / gas connections | 9.52 / 15.9 mm outside diameter, flare |
| Drain connection | VP20: 20 mm internal / 26 mm external diameter |
| Drain pump | Standard, 625 mm listed lift |
| Air filter | Resin net |
| Casing | Unpainted galvanised steel plate |
The unit body height and built-in height describe different clearances. Allow the access, suspension, drainage and duct space shown in the dimensional and installation drawings. Rear or bottom suction can be selected to suit the layout. The standard drain pump supports flexible drainage routing within the manufacturer installation limits.
Controls and optional configurations
Wired, infrared and centralised control arrangements are listed in the databook. Multi-zoning and fresh-air intake are optional configurations, not assumed to be included with the indoor unit. Confirm the selected controller, accessories and compatible outdoor system before finalising the installation.
FXSQ-A catalogue and technical databook
Compare the FXSQ-A range and review the VRV system options. Both documents are available under Technical Downloads below the purchasing area. The 2015 catalogue includes FXSQ-A features alongside separate FBQ split-system tables; those FBQ system efficiencies do not describe this VRV indoor unit. For the A2VEB specifications above, use the newer 2021 databook, including its revised indoor power-input values.