Opens in a new tab

Daikin RXYTQ16U5YF

16.0 HP class · 45.0 kW nominal T1
VRV IV+ · Heat pump · R-410A

Daikin RXYTQ16U5YF is an 16 HP-class VRV IV+ heat pump outdoor unit for multi-zone cooling and heating. Nominal T1 cooling is 45.0 kW (153,550 Btu/h), with 35.1 kW nominal T3 cooling at 46°C.

  • R-410A refrigerant, inverter scroll compression and Variable Refrigerant Temperature control.
  • Outdoor cooling operation from −5°C to 55°C dry bulb.
  • Dimensions H × W × D: 1,685 × 1,240 × 765 mm; catalogue net weight: 283 kg.
  • Three-phase supply; indoor units and controls selected to suit the system.

AED  35,900.00

Technical Downloads

Daikin RXYTQ-U5YF VRV IV+ heat pump catalogue cover
RXYTQ-U5YF Series
VRV IV+ catalogue
PDF · 64 pages · 5.9 MB
Daikin RXYTQ-U5YF engineering data book cover
RXYTQ-U5YF Series
Engineering data book
PDF · 50 pages · 5.8 MB
Daikin RXYTQ16U5YF ESMA ECAS certificate preview
RXYTQ16U5YF
ESMA certificate
PDF · 6 pages · 1998 KB
Valid until 12 October 2026

Daikin RXYTQ16U5YF VRV IV+ heat pump outdoor unit

The 16 HP-class RXYTQ16U5YF serves a designed network of VRV indoor units in multi-room and multi-zone buildings. It provides 45.0 kW nominal cooling at T1 conditions and 45.0 kW nominal heating. HP identifies its VRV capacity class, rather than electrical input power.

Cooling capacity and hot-climate efficiency

Model / capacity class RXYTQ16U5YF / 16 HP
Nominal T1 cooling at 35°C 45.0 kW / 153,550 Btu/h
Nominal T3 cooling at 46°C 35.1 kW / 119,800 Btu/h
T1 power input, including indoor units 12.64 kW
T3 power input, including indoor units 12.10 kW
T3 outdoor-unit power input 11.71 kW
EER, T1 / T3 12.15 / 9.90 (Btu/h)/W
Cooling Seasonal Performance Factor, T3 18.29 (Btu/h)/W

T1 cooling uses indoor air at 27°C dry bulb / 19°C wet bulb and outdoor air at 35°C dry bulb. T3 uses indoor air at 29°C dry bulb / 19°C wet bulb and outdoor air at 46°C dry bulb, per the catalogue’s ISO 15042:2011 notes. The separate maximum T3 capacity of 38.6 kW applies at 19°C indoor wet bulb, 46°C outdoor dry bulb and a 130% indoor connection ratio, for limited hours. It is not the nominal capacity. The seasonal figure follows the catalogue’s ISO 16358-1:2013/AMD 1:2019 method.

Heating performance and operating range

Nominal heating capacity 45.0 kW / 153,550 Btu/h
Heating COP 3.48 kW/kW
Heating power input, including indoor units 12.92 kW
Outdoor cooling range −5 to 55°C dry bulb
Indoor cooling range 14 to 25°C wet bulb
Outdoor heating range −20 to 15.5°C wet bulb
Indoor heating range 15 to 27°C dry bulb

Nominal heating uses indoor air at 20°C dry bulb, outdoor air at 7°C dry bulb / 6°C wet bulb, 5 m equivalent refrigerant piping and no level difference. Operating limits do not imply nominal output at every temperature; use the project design conditions when selecting capacity.

Variable refrigerant temperature and compressor design

Variable Refrigerant Temperature (VRT) control adjusts refrigerant temperature to changing load and comfort requirements. The VRV IV+ scroll compressor uses back-pressure control to reduce internal refrigerant leakage during low-load operation. A refrigerant-cooled PCB and four-sided, three-row heat exchanger support the outdoor unit’s thermal design. The series also provides a seven-segment service display and supports VRV Configurator commissioning.

Dimensions and electrical requirements

Power supply 380–415 V / 3-phase / 50 Hz; 400 V / 3-phase / 60 Hz
Refrigerant R-410A
Dimensions H × W × D 1,685 × 1,240 × 765 mm
Catalogue net weight 283 kg
Nominal sound pressure 64 dB(A)
Compressor quantity 2

Plan the mounting arrangement around the 283 kg catalogue unit weight, service clearances and unobstructed airflow. Refrigerant pipe sizes, additional charge, wiring and protective devices must be selected for the installed system using the applicable engineering and installation information.

Indoor units and system selection

The catalogue lists connections to Daikin VRV indoor families including FXAQ-ARVM wall units and FXFSQ-ARV1 round-flow cassettes, alongside concealed ducted options. Confirm the exact indoor models, combination ratio, controls and piping design as a complete system. Indoor units, controllers and interfaces are not implied to be included with this outdoor-unit listing.

RXYTQ-U5YF selection in Dubai and the UAE

Compare the RXYTQ-U5YF range using nominal T1 and T3 cooling, heating performance and available installation space. Technical Downloads contains the original 64-page Daikin catalogue with the rating conditions and wider VRV lineup. Contact Coolwell on 800 26659355 for help selecting the outdoor unit and associated VRV equipment.

Brand

Daikin

Series

RXYTQ-U5YF

T1 Cooling Capacity (Btu/h)

153,550

T1 Cooling Capacity (HP)

16.0

T1 Cooling Capacity (kW)

45.0

T1 Cooling Capacity (Ton)

12.80

Daikin RXYTQ-U7YF VRV Outdoor Unit ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Technology ImageDaikin RXYTQ-U7YF VRV Outdoor Unit VRT ImageDaikin RXYTQ-U7YF VRV Outdoor Unit VRT ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Software ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Core Technologies ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Features ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Benefits ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Anti Corrosion ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Flexibility ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Madoka ImageDaikin RXYTQ-U7YF VRV Outdoor Unit Madoka Image