Daikin FXMQ140PBV1

4.5 Ton | 16.0 kW | 6 HP | 54,600 Btu/h

Daikin FXMQ140PBV1 is a ceiling-mounted ducted VRV indoor unit with nominal cooling of 16 kW (54,600 Btu/h) and heating of 18 kW.

  • 300 mm-high body for concealed installation.
  • 100 Pa rated external static pressure, adjustable from 50 to 140 Pa.
  • Three airflow settings: 46 / 39 / 32 m³/min (HH/H/L).
  • Single-phase 220–240 V, 50/60 Hz supply.

AED  5,150.00

Technical Downloads

Daikin FXMQ-PBV1 ducted technical databook cover
FXMQ-PBV1 Series
Technical data book
PDF · 60 pages · 15.2 MB

Daikin FXMQ140PBV1 ducted VRV indoor unit

The FXMQ140PBV1 belongs to the FXMQ-PBV1 ceiling-mounted ducted range. Its 16 kW net cooling and 18 kW net heating capacity can be matched to the room load while the unit is concealed above the ceiling. Air is distributed through a separately designed duct network and grilles. Assess capacity, duct resistance and service access together when selecting this indoor unit for a VRV system.

Cooling and heating specifications

Indoor model FXMQ140PBV1
Net cooling capacity 16 kW / 54,600 Btu/h
Net heating capacity 18 kW / 61,400 Btu/h
Manufacturer capacity class 6 HP
Indoor power input, cooling / heating 0.405 / 0.380 kW

Cooling ratings use 27°C dry bulb / 19°C wet bulb indoors and 35°C dry bulb outdoors. Heating ratings use 20°C dry bulb indoors and 7°C dry bulb / 6°C wet bulb outdoors. Both use rated external static pressure, 7.5 m equivalent piping length and zero height difference. Capacities include indoor fan motor heat. Listed indoor power input is at rated external static pressure and is not the consumption of the complete VRV system.

Airflow and adjustable static pressure

Airflow HH / H / L 46 / 39 / 32 m³/min
Rated external static pressure 100 Pa
Adjustable external static pressure 50–140 Pa, 10 stages
Air-filter pressure drop 10 Pa
Sound pressure HH / H / L 46 / 45 / 43 dB(A)
Fan Direct-drive sirocco fan

The remote controller allows 10 static-pressure settings for this model. Check the fan-performance curves against the installed duct network and include filter resistance: the stated ESP excludes the air-filter pressure drop. HH, H and L identify the three airflow settings. For input at maximum airflow and maximum static pressure, use the databook electrical characteristics rather than the rated input above.

Sound figures are anechoic-chamber conversion values measured 1.5 m below the unit centre. Actual installed levels may be higher because of ambient conditions and room reflections.

Dimensions and installation connections

Indoor body H × W × D 300 × 1,400 × 700 mm
Unit mass 46 kg
Electrical supply 1 phase, 220–240 V, 50/60 Hz
Liquid / gas pipe connections 9.5 / 15.9 mm, flare connections
Drain connection VP25: 32 mm external / 25 mm internal diameter
Casing Galvanised steel plate
Refrigerant control Electronic expansion valve
Temperature control Microprocessor thermostat for cooling and heating

The 300 mm dimension is the body height, not the full ceiling clearance required for installation. Use the dimensional drawings to allow space for suspension, duct connections, drainage, pipework and maintenance.

Filters and system selection

The specification lists a standard pre-filter. High-efficiency and long-life filters are optional accessories; the notes call for suitable suction-side duct filtration with at least 50% dust collection efficiency by the stated gravity method. Confirm the selected filter arrangement and include its pressure drop in the duct design. Safety devices listed in the databook are a fuse and fan-driver overload protector.

FXMQ-PBV1 technical downloads

Compare the FXMQ-PBV1 range by cooling load, airflow, sound and available installation space. Confirm the VRV outdoor-unit and controller combination for the complete system. The original 60-page engineering databook is available in Technical Downloads below the purchasing area, including specifications, dimensions, electrical data, capacity tables, fan curves and installation guidance.

Brand

Daikin

Series

FXMQ-PBV1

T1 Cooling Capacity (Btu/h)

54,600

T1 Cooling Capacity (HP)

6

T1 Cooling Capacity (kW)

16.0

T1 Cooling Capacity (Ton)

4.5

Daikin FXMQ-PBV1 VRV Concealed Ducted Features ImageDaikin FXMQ-PBV1 manufacturer specifications, databook page 6Daikin FXMQ-PBV1 manufacturer specifications, databook page 7Daikin FXMQ-PBV1 manufacturer specifications, databook page 8