Daikin RXQ6ARYFK VRV X outdoor unit
The 6 HP-class RXQ6ARYFK supplies cooling to a designed network of Daikin VRV indoor units. It is a cooling-only outdoor unit for multi-room and multi-zone applications, with 16.0 kW nominal T1 capacity and 14.7 kW nominal T3 capacity. The HP value identifies the VRV capacity class; it is not the electrical input power.
Cooling performance and efficiency
| Model / capacity class | RXQ6ARYFK / 6 HP |
|---|---|
| Nominal T1 cooling | 16.0 kW / 54,600 Btu/h |
| Nominal T3 cooling | 14.7 kW / 50,000 Btu/h |
| T1 power input, including indoor units | 4,500 W |
| T3 power input, including indoor units | 5,100 W |
| T3 outdoor-unit power input | 4,610 W |
| EER, T1 / T3 | 3.56 / 2.88 W/W |
| CSPF T3 for hot climates | 4.76 W/W |
| Cooling operation range | 10–52°C outdoor dry bulb |
T1 ratings use indoor air at 27°C dry bulb / 19°C wet bulb and outdoor air at 35°C dry bulb. T3 ratings use indoor air at 29°C dry bulb / 19°C wet bulb and outdoor air at 46°C dry bulb. The catalogue bases these ratings on ISO 15042:2011 and the seasonal figure on ISO 16358-1:2013/AMD 1:2019.
The separate maximum T3 cooling figure of 14.8 kW applies at 19°C indoor wet bulb, 46°C outdoor dry bulb and a 130% indoor-unit connection ratio, for a limited number of hours. It is not the nominal T3 rating. The 52°C operating limit also does not imply nominal capacity at that temperature.
Variable refrigerant temperature and high-ambient design
Variable Refrigerant Temperature (VRT) control adjusts refrigerant temperature together with inverter compressor speed as the cooling load changes. The VRV X series combines scroll compression with a three-row heat exchanger and anti-corrosion fin treatment. A refrigerant-cooled inverter PCB supports operation in high ambient temperatures. The catalogue specifies outdoor external static pressure up to 78.4 Pa, subject to the installation design.
Dimensions, refrigerant and connections
| Power supply | 380–415 V / 3-phase / 50 Hz; 400 V / 3-phase / 60 Hz |
|---|---|
| Refrigerant / listed charge | R-410A / 5.9 kg |
| Compressor type / quantity | Hermetically sealed scroll / 1 |
| Outdoor airflow | 178 m³/min |
| Dimensions H × W × D | 1,657 × 930 × 765 mm |
| Net machine weight | 165 kg |
| Catalogue sound level | 56 dB(A) |
| Liquid / gas piping connections | 9.5 / 19.1 mm |
| Indoor-unit combination ratio | 50–130% |
| Casing colour | Ivory white |
Allow for the 165 kg machine weight, service access and outdoor airflow when planning its location. The listed refrigerant charge is a catalogue unit value; final system charge and refrigerant pipe sizing depend on the connected indoor units and piping design.
Indoor units, controls and system selection
The catalogue’s indoor lineup includes FXAQ-ARVM wall units, FXFSQ-ARV1 round-flow cassettes and several concealed ducted ranges. Indoor-unit selection, connection ratio, controls and piping must be checked as a complete system. The stated 50–130% combination ratio is not a guarantee of simultaneous full output from every connected indoor unit.
Individual wired controls and central-management interfaces are described in the catalogue. Confirm the controller, interface and indoor-unit requirements for the project; they are not implied to be included with this outdoor-unit listing.
RXQ-ARYFK selection in Dubai and the UAE
Compare the RXQ-ARYFK range by nominal cooling capacity, high-ambient performance, electrical supply and installation space. Download the original 34-page Daikin VRV X catalogue in Technical Downloads for the full lineup and rating notes. Contact Coolwell on 800 26659355 for help selecting the outdoor unit and associated VRV equipment.